Model | PWR101 (110V) | PWR102 (220V) |
Rated Voltage | 150V AC | 275V AC |
Discharge Voltage
(L-L) | | 500V (RMS 300V) |
Discharge Voltage
(L-G) | | 700V (RMS 300V) |
Max. Clamping
Voltage | | AC 775V |
Nominal Voltage | 100/110/120V AC | 200/220/240V AC |
Response Time | 5 nsec or less |
Nominal Impulse
Discharge Current | 10kA / mode (8 x 20 uS) 30kA / Total (8 x 20 uS) |
Maximum Load
Current | 2A |
Max. Line Voltage (V DC) | 385V |
Current Leakage
Between Line (L-L) | 0.1mA or less |
Current Leakage
Line to ground (L-G) | 0.1mA or less |
Insulation
Resistance | 100㏁ or more |
Ambient Temperature
and Humidity | -40℃ ~ 80℃
/ 90% RH |
Elements | UL Approved
Parts |
Featured Function | Automatic Return after Surge Inflow |
Case Material
& Color | Flame-resistant Resin
/ Black |
Mounting | Plug-in Type, Base & Body Separable |
Weight | 100g |
Dimensions | 22(W) x 75(H) x 85(D) mm |