Home

Contact us

 

 

HYUNDAI   HiAN10   Air Circuit Breaker

UAN

UAS

HiAN

HiAS

HiAN06

HiAN08

HiAN10

HiAN12

HiAN16

HiAN20

HiAN25

HiAN32

HiAN40

HiAN50

HiAN63

Model

HiAN10

Rated current (A)

1,000

Rated neutral phase current (A)

1,000

Number of poles

3, 4

Utilization category

B

Rated primary current of ACB protection relay [ICT] (A)

160

320

630

800

1,000

Rated insulation voltage (Ui) (V)

AC1,000

Rated operation voltage (Ue) (V)

AC690

Rated breaking capacity (kA sym) [lcu]

IEC, VDE, BS, AS

with Inst. Icu=100% lcs

AC690V

50

AC500V

70

AC415V below

70

without Inst. (MCR)

AC600V

50

AC500V below

70

Rated making capacity (kA peak) [lcm]

IEC, VDE, BS, AS

with Inst. Icu=100% lcs

AC690V

105

AC500V

154

AC415V below

154

without Inst. (MCR)

AC600V

105

AC500V below

154

Rated impulse withstand voltage (Uimp) [kV]

8

Rated short-time withstand current [lcw] (kA r.m.s)

1sec

65

Rated latching current (kA)

65

Total breaking time (sec)

0.04

Closing operating time

Charging time (sec) max.

10

Closing time (sec) max.

0.04

Durability

Mechanical

without maintenance

10,000

with maintenance

20,000

Electrical

without maintenance

5,000

with maintenance

10,000

Samcheondong 1Ga 651-2 Wansangu Jeonjusi Jeonbuk 560-807 KOREA

Tel : +82-63-228-0560   Fax : +82-63-228-0561   e-mail : akorm@akorm.com   Website : www.akorm.com/industrial

Copyright (C)   AKORM Corporation   All Rights Reserved