Model |
HiAN32 |
Rated current (A) |
3,200 |
Rated neutral phase current
(A) |
3,200 |
Number of poles |
3, 4 |
Utilization category |
B |
Rated primary current
of ACB protection relay [ICT] (A) |
1,000 |
1,600 |
2,000 |
2,500 |
3,200 |
Rated insulation voltage (Ui)
(V) |
AC1,000 |
Rated operation voltage (Ue)
(V) |
AC690 |
Rated
breaking capacity (kA
sym) [lcu]
IEC,
VDE, BS, AS |
with Inst.
Icu=100% lcs |
AC690V |
65 |
AC500V |
85 |
AC415V
below |
85 |
without Inst.
(MCR) |
AC600V |
65 |
AC500V
below |
85 |
Rated
making capacity (kA
peak) [lcm]
IEC,
VDE, BS, AS |
with Inst.
Icu=100% lcs |
AC690V |
143 |
AC500V |
187 |
AC415V
below |
187 |
without Inst.
(MCR) |
AC600V |
143 |
AC500V
below |
187 |
Rated
impulse withstand voltage (Uimp) [kV] |
8 |
Rated
short-time withstand current [lcw] (kA r.m.s) |
1sec |
85 |
Rated
latching current (kA) |
85 |
Total
breaking time (sec) |
0.04 |
Closing
operating time |
Charging time (sec) max. |
10 |
Closing time (sec) max. |
0.04 |
Durability |
Mechanical |
without
maintenance |
10,000 |
with maintenance |
20,000 |
Electrical |
without
maintenance |
3,000 |
with maintenance |
5,000 |
|