Model

HiAN40

Rated current (A)

4,000

Rated neutral phase current (A)

4,000

Number of poles

3, 4

Utilization category

B

Rated primary current of ACB protection relay [ICT] (A)

3,200

4,000

Rated insulation voltage (Ui) (V)

AC1,000

Rated operation voltage (Ue) (V)

AC690

Rated breaking capacity (kA sym) [lcu]

IEC, VDE, BS, AS

with Inst. Icu=100% lcs

AC690V

85

AC500V

100

AC415V below

100

without Inst. (MCR)

AC600V

85

AC500V below

100

Rated making capacity (kA peak) [lcm]

IEC, VDE, BS, AS

with Inst. Icu=100% lcs

AC690V

187

AC500V

220

AC415V below

220

without Inst. (MCR)

AC600V

187

AC500V below

220

Rated impulse withstand voltage (Uimp) [kV]

8

Rated short-time withstand current [lcw] (kA r.m.s)

1sec

75

Rated latching current (kA)

75

Total breaking time (sec)

0.04

Closing operating time

Charging time (sec) max.

10

Closing time (sec) max.

0.06

Durability

Mechanical

without maintenance

5,000

with maintenance

10,000

Electrical

without maintenance

2,000

with maintenance

5,000