|
Model |
N100-037HF |
|
Output |
Applicable motor capacity (kW) |
3.7 |
|
Rated output capacity (kVA) |
7.6 |
|
Rated output current (A) |
9.2 |
|
Rated output voltage (V) |
3-phase, 380~480 V |
|
Maximum output frequency (Hz) |
400 Hz |
|
Power
supply |
Phase, Voltage, Frequency |
Three-phase, 380~480 VAC, 50/60 Hz |
|
Power Conditions |
Voltage: ±10% / frequency: ±5% |
|
Control
characteristic |
Control system |
Space vector PWM control |
|
Torque control |
V/F control, sensorless vector control |
|
Output frequency range |
0.01~400 Hz |
|
Frequency
setting resolution |
Analog |
Max. setting frequency÷500 (DC 5 V input) Max. setting
frequency÷1000 (DC10 V, 4~20 mA input) |
|
Digital |
0.01 Hz (100 Hz and less ), 0.1 Hz (100 Hz or more ) |
|
Frequency
precision |
Analog |
Within 0.1% of maximum output frequency |
|
Digital |
Within 0.01% of maximum output frequency |
|
Voltage/frequency characteristic |
Any base frequency setting possible between 0 Hz and 400 Hz,
constant torque or variable torque pattern selectable |
|
Overload rating |
150% of rated current for 60 sec |
|
Starting torque |
More than 200% (at 0.5 Hz) |
|
Torque boost |
Manual torque boost can be set between 0~50% |
|
Acceleration/deceleration time setting |
0.1~3000 sec setting possible |
|
Acceleration/deceleration pattern |
linear, S-curve, U-curve selection possible |
|
Braking torque |
Dynamic |
150% (5 sec) |
|
DC
braking |
Operating frequency (0~10 Hz), operating time (1~10 sec),
operating braking force (0~50%) variable External DC braking setting possible |
|
Current stall prevention
operation level |
Operation current level setting possible (20~200% variable),
enable/disable selection |
|
Voltage stall prevention
operation level |
Operation level constant, enable/disable selection |