Order Code |
UAN32B |
Frame |
B frame |
Rated current (In max at 40˚C) (A) |
3,200 |
Rated operating voltage (Ue) (V) |
AC690 |
Rated insulation voltage (Ui) (V) |
AC1,000 |
Frequency (Hz) |
50/60 |
Number of poles |
3, 4 |
Current setting range (….. x In max) |
0.4 - 1.0 |
Rated current of neutral pole (…..% x In) |
100% |
Rated breaking
capacity
(Icu)
(kA sym) |
IEC 60947-2
category “B”
KS C 4620 |
AC690/600/550V |
85 |
AC500/480/460V |
100 |
AC415/380/230/220V |
100 |
Rated service breaking capacity (…..% x Icu) |
100% |
Rated making
capacity
(Icm)
(kA peak) |
IEC 60947-2
category “B”
KS C 4620 |
AC690/600/550V |
187 |
AC500/480/460V |
220 |
AC415/380/230/220V |
220 |
Rated short-time capacity
(Icw)
(kA, without Inst.) |
1 sec |
85 |
2 sec |
75 |
3 sec |
65 |
Rated impulse withstand voltage (Uimp) (kV) |
12 |
Maximum total breaking time (ms) |
40 |
Closing operating time |
Motor charging time (sec) max. |
10 |
Closing time (ms) max. |
80 |
Life cycle (times) |
Mechanical |
Without maintenance |
15,000 |
With maintenance |
20,000 |
Electrical |
Without maintenance |
5,000 |
With maintenance |
10,000 |
Weight (kg) |
3 pole |
Draw-out type |
87 |
Fixed type |
44 |
4 pole |
Draw-out type |
116 |
Fixed type |
55 |
External dimension
(mm)
(WxHxD, except busbar) |
3 pole |
Draw-out type |
399
x 460 x 368 |
Fixed type |
408
x 404 x 296 |
4 pole |
Draw-out type |
514
x 460 x 368 |
Fixed type |
523
x 404 x 296 |