Order Code |
UAN63D |
Frame |
D frame |
Rated current (In max at 40˚C) (A) |
6,300 |
Rated operating voltage (Ue) (V) |
AC690 |
Rated insulation voltage (Ui) (V) |
AC1,000 |
Frequency (Hz) |
50/60 |
Number of poles |
3, 4 |
Current setting range (….. x In max) |
0.4 - 1.0 |
Rated current of neutral pole (…..% x In) |
100% |
Rated breaking
capacity
(Icu)
(kA sym) |
IEC 60947-2
category “B”
KS C 4620 |
AC690/600/550V |
100 |
AC500/480/460V |
150 |
AC415/380/230/220V |
150 |
Rated service breaking capacity (…..% x Icu) |
100% |
Rated making
capacity
(Icm)
(kA peak) |
IEC 60947-2
category “B”
KS C 4620 |
AC690/600/550V |
220 |
AC500/480/460V |
330 |
AC415/380/230/220V |
330 |
Rated short-time capacity
(Icw)
(kA, without Inst.) |
1 sec |
100 |
2 sec |
100 |
3 sec |
100 |
Rated impulse withstand voltage (Uimp) (kV) |
12 |
Maximum total breaking time (ms) |
40 |
Closing operating time |
Motor charging time (sec) max. |
10 |
Closing time (ms) max. |
80 |
Life cycle (times) |
Mechanical |
Without maintenance |
10,000 |
With maintenance |
15,000 |
Electrical |
Without maintenance |
2,000 |
With maintenance |
5,000 |
Weight (kg) |
3 pole |
Draw-out type |
210 |
Fixed type |
120 |
4 pole |
Draw-out type |
280 |
Fixed type |
160 |
External dimension
(mm)
(WxHxD, except busbar) |
3 pole |
Draw-out type |
766
× 460 × 368.4 |
Fixed type |
775.4
× 404.4 × 295.8 |
4 pole |
Draw-out type |
996
× 460 × 368.4 |
Fixed type |
1,005
× 404.4 × 295.8 |