General Specifications
Rated Insulation Voltage, Ui 1,000 V Suitability for Isolation

Yes

Rated Operational Voltage, Ue 690 V Utilization Category

A

Impulse Withstand Voltage, Uimp 8 kV Pollution Degree

3

Protective Function Overload, short-circuit and instantaneous protection Reference Standard

IEC 60947-2

 

Model

HGM100

HGM125

Frame (AF)

100

125

Pole (P)

2, 3, 4

Rated current, at 40 ℃ (A)

16, 20, 25, 32, 40, 50, 63, 75, 80, 100

16, 20, 25, 32, 40, 50, 63, 75, 80, 100, 125

Rated

short-circuit

breaking

capacity [Icu]

(kA rms)

Recognition code

for order

HGM100E

HGM100S

HGM100H

HGM100L

HGM125E

HGM125S

HGM125H

HGM125L

AC660/690 V

2.5

5

7.5

8

5

7.5

8

10

AC480/500 V

7.5

10

14

26

10

14

26

35

AC440/460 V

16

20

26

30

20

26

38

55

AC380/415 V

16

20

26

30

20

26

38

55

AC220/240 V

35

50

50

50

50

65

85

100

DC250 V (2P)

5

10

15

15

10

15

20

30

Service breaking capacity

[Ics = % Icu]

100

100

75

50

100

Endurance

(Durability)

Mechanical

30,000

Electrical

10,000

Trip Device

Thermal

magnetic

Long

time

[LT]

Fixed

(1.0) x In

Adjustable 

(0.8 - 0.9 - 1.0) x In

Instantaneous

[INST]

16 - 32 A: 400 A, 40 - 100 A: 10 x In

16 - 32 A: 400 A, 40 - 125 A: 10 x In

 

Samcheondong 1Ga 651-2 Wansangu Jeonjusi Jeonbuk 560-807 KOREA

Tel : +82-63-228-0560   Fax : +82-63-228-0561   e-mail : akorm@akorm.com   Website : www.akorm.com/industrial