HYUNDAI
HGM800 Molded
Case Circuit Breaker (MCCB)
General
Specifications |
Rated Insulation Voltage, Ui |
1,000 V |
Suitability for Isolation |
Yes |
Rated Operational Voltage, Ue |
690 V |
Utilization Category |
A |
Impulse Withstand Voltage, Uimp |
8 kV |
Pollution Degree |
3 |
Protective Function |
Overload, short-circuit and instantaneous protection |
Reference Standard |
IEC 60947-2 |
Model |
HGM800 |
Frame (AF) |
800 |
Pole (P) |
2, 3, 4 |
Rated
current, at 40 ℃ (A) |
700, 800 |
Rated
short-circuit
breaking
capacity
[Icu]
(kA rms)
|
Recognition code for order |
HGM800S |
HGM800H |
HGM800L |
AC660/690 V |
8 |
10 |
14 |
AC480/500 V |
45 |
50 |
65 |
AC440/460 V |
50 |
70 |
85 |
AC380/415 V |
65 |
85 |
100 |
AC220/240 V |
75 |
100 |
125 |
DC250 V (2P) |
25 |
40 |
40 |
Service
breaking capacity [Ics = % Icu] |
100 |
Endurance
(Durability) |
Mechanical |
2,500 |
Electrical |
500 |
Trip Device
Thermal
magnetic
|
Long time
[LT] |
Fixed |
(1.0) x In |
Adjustable |
(0.63 - 0.8 - 1.0) x In |
Instantaneous [INST] |
10 x In |
|
|