HYUNDAI
HGM160 & HGM250 Molded
Case Circuit Breaker (MCCB)
General
Specifications |
Rated Insulation Voltage, Ui |
1,000 V |
Suitability for Isolation |
Yes |
Rated Operational Voltage, Ue |
690 V |
Utilization Category |
A |
Impulse Withstand Voltage, Uimp |
8 kV |
Pollution Degree |
3 |
Protective Function |
Overload, short-circuit and instantaneous protection |
Reference Standard |
IEC 60947-2 |
Model |
HGM160 |
HGM250 |
Frame (AF) |
160 |
250 |
Pole (P) |
2, 3, 4 |
Rated
current, at 40 ℃ (A) |
100, 125, 150, 160 |
100, 125, 150, 160, 175,
200, 225, 250 |
Rated
short-circuit
breaking
capacity [Icu]
(kA rms) |
Recognition code
for order
|
HGM160E |
HGM160S |
HGM160H |
HGM160L |
HGM250E |
HGM250S |
HGM250H |
HGM250L |
AC660/690 V |
7.5 |
8 |
8 |
10 |
7.5 |
8 |
8 |
10 |
AC480/500 V |
14 |
20 |
26 |
35 |
14 |
20 |
26 |
35 |
AC440/460 V |
20 |
26 |
38 |
55 |
20 |
26 |
38 |
55 |
AC380/415 V |
20 |
26 |
38 |
55 |
20 |
26 |
38 |
55 |
AC220/240 V |
50 |
65 |
85 |
100 |
50 |
65 |
85 |
100 |
DC250 V (2P) |
10 |
15 |
20 |
30 |
10 |
15 |
20 |
30 |
Service
breaking capacity
[Ics = % Icu]
|
100 |
Endurance
(Durability) |
Mechanical |
25,000 |
Electrical |
10,000 |
Trip Device
Thermal
magnetic |
Long
time
[LT] |
Fixed |
(1.0) x In |
Adjustable |
(0.8 - 0.9 - 1.0) x In |
Instantaneous [INST] |
10 x In |
|
|