Home

Contact us

 

HYUNDAI HGP100 High Performance Motor Protection Circuit Breaker (MCCB)

General Specifications
Rated Insulation Voltage, Ui 1,000 V Suitability for Isolation

Yes

Rated Operational Voltage, Ue 690 V Utilization Category

A

Impulse Withstand Voltage, Uimp 8 kV Pollution Degree

3

Protective Function Short-circuit and instantaneous protection Reference Standard

IEC 60947-2

 

Model

HGP100

Frame (AF)

100

Pole (P)

3

Rated current at 40°C (A)

2.5, 3.2, 6.3, 12.5, 20, 32, 50, 63, 80, 100

Rated short-circuit
breaking capacity
[Icu] (kA rms)
Recognition code for order

HGP100S

HGP100H

HGP100L

AC660/690 V

8

8

10

AC480/500 V

50

65

85

AC440/460 V

65

85

130

AC380/415 V

85

100

130

AC220/240 V

100

130

150

Service breaking capacity [Ics = % Icu]

100

Endurance (Durability) Mechanical

25,000

Electrical

10,000

Trip Device
Thermal Magnetic
Instantaneous [INST]

(6 - 7 - 8 - 9 - 10 - 11 - 12 - 13) x In

 

Samcheondong 1Ga 651-2 Wansangu Jeonjusi Jeonbuk 560-807 KOREA

Tel : +82-63-228-0560   Fax : +82-63-228-0561   e-mail : akorm@akorm.com   Website : www.akorm.com/industrial