HYUNDAI
HGP125D High Performance
Molded
Case Circuit Breaker (MCCB)
| General
Specifications |
| Rated Insulation Voltage, Ui |
1,000 V |
Suitability for Isolation |
Yes |
| Rated Operational Voltage, Ue |
690 V |
Utilization Category |
A |
| Impulse Withstand Voltage, Uimp |
8 kV |
Pollution Degree |
3 |
| Protective Function |
Overload, short-circuit and instantaneous protection |
Reference Standard |
IEC 60947-2 |
| Model |
HGP125D |
| Frame (AF) |
125 |
| Pole (P) |
3, 4 |
| Rated
current at 40°C (A) |
16, 20, 25, 32, 40, 50, 63, 75, 80, 100, 125 |
Rated
short-circuit breaking capacity [Icu] (kA
rms) |
Recognition code for order |
HGP125DS |
HGP125DH |
HGP125DL |
HGP125DX |
| AC660/690 V |
8 |
8 |
10 |
10 |
| AC480/500 V |
50 |
65 |
85 |
100 |
| AC440/460 V |
65 |
85 |
130 |
150 |
| AC380/415 V |
85 |
100 |
130 |
150 |
| AC220/240 V |
100 |
130 |
150 |
200 |
| DC250 V |
65 |
85 |
100 |
100 |
| Service
breaking capacity [Ics = % Icu] |
100 |
| Endurance (Durability) |
Mechanical |
25,000 |
| Electrical |
10,000 |
Trip Device Thermal
Magnetic |
Long time [LT] |
(0.8 - 0.9 - 1.0) x In |
| Instantaneous [INST] |
16 - 32 A: 400 A, 40 - 125 A: 10 x In |
|
|