Home

Contact us

 

HYUNDAI HGP400 High Performance Molded Case Circuit Breaker (MCCB)

General Specifications
Rated Insulation Voltage, Ui 1,000 V Suitability for Isolation

Yes

Rated Operational Voltage, Ue 690 V Utilization Category

A

Impulse Withstand Voltage, Uimp 8 kV Pollution Degree

3

Protective Function Overload, short-circuit and instantaneous protection Reference Standard

IEC 60947-2

 

Model

HGP400

Frame (AF)

400

Pole (P)

3, 4

Rated current at 40°C (A)

300, 350, 400

Rated short-circuit
breaking capacity
[Icu] (kA rms)
Recognition code for order

HGP400S

HGP400H

HGP400L

HGP400X

AC660/690 V

10

20

25

35

AC480/500 V

50

70

85

100

AC440/460 V

70

85

130

150

AC380/415 V

85

100

130

150

AC220/240 V

100

130

150

200

DC250 V

65

85

100

100

Service breaking capacity [Ics = % Icu]

100

Endurance (Durability) Mechanical

20,000

Electrical

6,000

Trip Device
Thermal Magnetic
Long time [LT]

(0.8 - 0.9 - 1.0) x In

Instantaneous [INST]

(5 - 6 - 7 - 8 - 9 - 10) x In

 

Samcheondong 1Ga 651-2 Wansangu Jeonjusi Jeonbuk 560-807 KOREA

Tel : +82-63-228-0560   Fax : +82-63-228-0561   e-mail : akorm@akorm.com   Website : www.akorm.com/industrial

Copyright (C)   AKORM Corporation   All Rights Reserved