HYUNDAI
HGP630 High Performance
Molded
Case Circuit Breaker (MCCB)
| General
Specifications |
| Rated Insulation Voltage, Ui |
1,000 V |
Suitability for Isolation |
Yes |
| Rated Operational Voltage, Ue |
690 V |
Utilization Category |
A |
| Impulse Withstand Voltage, Uimp |
8 kV |
Pollution Degree |
3 |
| Protective Function |
Overload, short-circuit and instantaneous protection |
Reference Standard |
IEC 60947-2 |
| Model |
HGP630 |
| Frame (AF) |
630 |
| Pole (P) |
3, 4 |
| Rated current at
40°C (A) |
500, 630 |
Rated short-circuit breaking capacity [Icu] (kA rms) |
Recognition
code for order |
HGP630S |
HGP630H |
HGP630L |
HGP630X |
| AC660/690 V |
10 |
20 |
25 |
35 |
| AC480/500
V |
50 |
70 |
85 |
100 |
| AC440/460
V |
70 |
85 |
130 |
150 |
| AC380/415
V |
85 |
100 |
130 |
150 |
| AC220/240
V |
100 |
130 |
150 |
200 |
| DC250
V |
65 |
85 |
100 |
100 |
| Service
breaking capacity [Ics = % Icu] |
100 |
| Endurance (Durability) |
Mechanical |
20,000 |
| Electrical |
4,000 |
Trip Device Thermal Magnetic |
Long
time [LT] |
(0.8 - 0.9 - 1.0) x In |
| Instantaneous
[INST] |
(5 - 6 - 7 - 8 - 9 - 10) x In |
|
|